7% Dry Type Iron Core Reactor

Characteristics

  • Highest linearity
  • Temperature control via micro switch in inner coil
  • Highest life time by high quality materials
  • Low losses
  • High overloading capability
  • Safety device, temperature micro switch
  • Low noise

Technical Data

%Drop

KVAR

400V

41

5V

44

0V

52

5V

WT(KG)

W

I(A)

L(mH)

I(A)

L(mH)

I(A)

L(mH)

I(A)

L(mH)

7%

5

7.22

7.668

7

8.4

6.56

9.3

5.5

13.2

5.5

33

10

14.43

3.837

14

4.2

13.12

4.65

11

6.6

12.2

90

15

21.65

2.557

21

2.8

19.68

3.1

16.5

4.4

12.5

90

25

36.08

1.534

35

1.68

32.8

1.86

27.5

2.64

18

120

50

72.17

0.767

70

0.84

65.6

0.93

55

1.32

26

200

75

108.25

0.511

105

0.56

98.4

0.621

82.5

0.88

50

300

100

144.34

0.384

140

0.42

131.2

0.465

110

0.66

60

350

1) Voltage rise up to 106% of rated voltage is considered in current Ieff. 2) Ieff = √ (I12 + I32 + ...Ix2 )

Line 1U1-1V1-1W1
Capacitors 1U2-1V2-1W2
Temperature control 1-2

  • Do not install the reactor in case of any visible damages.
  • Installation must be done by skilled personnel only.
  • Do not use or store harmonic filter reactors in corrosive atmosphere, especially where chloride gas, sulphide gas, acid, alkali, salt or similar substances are present.
  • Do not touch the device during operation: all electrically active parts of this equipment such as windings, electronic components, leads, fuses and terminals carry a dangerous voltage which can lead to burns or electric shock.
  • Covers which protect these electrically active parts from being touched must not be opened or removed during operation.
  • Before any assembly or maintenance work is started, all installations and equipment must be disconnected from the power source.
  • Noncompliance with these instructions may lead to death, serious injury or major damage to equipment.

FAILURE TO FOLLOW CAUTIONS MAY RESULT, WORST CASE, IN PREMATURE FAILURES OR PHYSICAL INJURY.