News
...
DCU

Data Concentrator with Metering Part

Description

  • Active energy, accuracy class 0,5S, export and import
  • Reactive energy, accuracy class 1
  • Non-volatile memory
  • Up to 6 tariff registers, up to 24 changeovers per day
  • Up to 2 built-in extra relays (2 or 5A) for load control
  • Energy quality control & monitoring
  • Terminal box and meter case opening sensors
  • Strong external magnetic field sensor
  • Standard data model, open protocols
  • Universal Hardware Platform supporting OFDM based technologies: PRIME 1.3.6, PRIME 1.4, G3-PLC
  • USB, wM-BUS, RS-485 interfaces
  • Calculation of total harmonic distortion factor
  • High-level security
  • 2G/3G/4G support
  • Prepayment & credit operational modes
  • Backup power supply
  • IP 54 protection against water and dust

Specifications

Electric Energy Measurement Range:- Active (Reactive) Energy 0 to 2∙109 Wh (VAr∙h)
Electric power measurement range:- active (reactive, full) power 0 to 108 W (VAr, V∙A)
Limits of permissible absolute error when measuring:- active electric energy, Wh - reactive electric energy, VAr∙h - active electric power, Wh - reactive electric power, VAr - apparent electric power, V∙A ± 1
Absolute error of hours per day, with external synchronization at least once every 3 hours, not more than ± 0.5 s/day
Absolute error of hours per day in the absence of external synchronization at temperatures from -40 °C to + 70 °C, not more than ± 3 s/day
Interval between verifications 10 years
Nominal Phase Voltage 230 V
Operating Phase Voltage Range 100 V to 350 V
Rated Frequency and Operating Range 50 Hz ± 2.5 Hz
Active power consumption, not more than 12 Watts
Total power consumption, max 30 V∙A
External DC UPS Voltage Rating 12 to 24 V
Current drawn from external UPS is not more than 2 A
Interfaces for Local Connectivity Optoport, 9,600 bps;- USB-host, Type A, USB 2.0, 12 Mbps
Interfaces for communication with the CPI and synchronization of the built-in clock in the UDPD GSM/GPRS -1 modem, 2 Micro-SIM card slots;- Ethernet - 2 independent ports, simultaneous, independent, RJ45 connector, 10/100 Mbps
Interfaces for exchanging data with counters and synchronizing counter clocks 868 MHz radio channel, 9 600 bps;- two-wire RS-485, 9 600 bps;- PLC LV (0.4 kV) - 1 three-phase modem
Maximum Number of Connected Counters 1000 pcs.
Sensors opening the case;- opening the cover of the connector panel
Degree of sheath protection IP 51
Service life of the device:- average service life, not less than - mean time between failures, not less than 24 years 180,000 h
Average time to recovery, no more than 24 hrs
Dimensions (241×170×86) mm
Weight, not more than 1.3 kg