Description

1/3 Phase 11 kV Vacuum Contactor Switch for Indoor Application, available in both for with Mechanical Latch / permanent Magnetic Latch type Mechanism. Vacuum Contactor having options of different auxiliary supply voltages and auxiliary contacts.

Technical Specifications

Application Indoor Reference Standard IEC 62271-1/103
Rated Voltage 3.3kV/6.6kV/11kV Frequency 50Hz
Rated current 400A Rated capacitor switching current 100/200A
Rated short circuit current 10kA rms for 1 sec. Rated short circuit breaking current 3.2kA rms
Rated short circuit making current 4kA peak Basic Insulation Level 28kV rms / 95kV peak
Switch class C1 Closing time 115ms
Opening time 50ms Auxiliary Contacts 1NO+2NC / 3NO+4NC
Auxiliary control Voltage 110V AC/DC or 220V AC/DC No. of Closing coils in each VC 2 Nos.
No. of Tripping coils in each VC 1 No. in mechanical latch type VC