- Intelligent Control
- Menu driven handling in English language
- Test-run possible
- Large voltage measuring range
- Recall function of recorded values
- Four-quadrant operation
- Potential free contact alarm output (Optional)
- RS485 communication interface (Optional)
- Real Time Clock (Optional)
- Log of Time date stamping for last 3 system faults enabled
- Auto Initialization function
- Input voltage connection detection (L-N\L-L)
- Input Phase correction angle detection
- Number of capacitor bank connected
- Three bank selection mode
- Control series (up to 20)
- User defined capacitor bank kvar
- Auto detected capacitor bank kvar
Display |
|
---|---|
System parameters displayed |
|
Alarm output |
|
Recall recorded values |
|
Warning Messages |
|
Weight | 0.57 kg |
---|---|
Case | Panel-mounted instrument, 144 × 144 × 56 mm (cut out 142 +0.8× 142+0.8 mm) |
Ambient conditions | |
Over-voltage class | III |
Pollution degree | 2 |
Operating temperature | –10 ... +60 °C |
Storage temperature | –20 ... +65 °C |
Sensitivity to EMC | IEC61326-1 |
Safety guidelines | IEC 61010-1:2010 |
Mounting position | Flush Mounting |
Humidity class | 15% … 95% non-condensing |
Protection class | |
Front plate | IP54 to IEC60529 |
Rear side | IP20 to IEC60529 |
Operation | |
Auxiliary Supply voltage | 110 V AC – 550VAC |
Auxiliary Supply Frequency | 40 to 70 Hz |
Target cos phi | 0.8 ind. … 0.8 cap. |
Switching On & Off | 10 s … 30 min |
Discharge Time | 60 s … 30 min |
Control modes | self-optimized intelligent control mode |
Measurement | |
Measurement voltage range | 30 ... 550 V AC (L–L / L–N) |
Fundamental frequency | 50 / 60 Hz |
Measurement current (CT) | x/5 and x/1 Ampere onsite programmable |
Minimum operating current | 2 mA |
Maximum current | 6 A (sinusoidal) |
Accuracy | Current, voltage: 0.5% of nominal value Active, apparent power: 1% of nominal value Active Energy : 1% Apparent Energy : 1% Reactive Energy : 2% THD : ± 4% |
Switching outputs Relay outputs |
|
Number of outputs | 6 / 8 / 12 steps available |
Switching voltage/Power | Max. 250 VAC / 1000W |
Alarm relay | Potential-free contact (Max. 250 VAC / 1000W) |
Type | Voltage | Output Relay | Alarm output | Interface (RS485) | RTC | Ordering code |
---|---|---|---|---|---|---|
50/60 Hz | ||||||
BR2100 | 240 | 6 | Yes | No | No | B44066R2006R240 |
BR2100 | 240 | 8 | Yes | No | No | B44066R2008R240 |
BR2100 | 240 | 12 | Yes | No | No | B44066R2012R240 |
Please read cautions information about PFC capacitors and cautions as well as installation and maintenance instructions in the actual version of the Product Profile Power Factor Correction to ensure optimum performance and prevent products from failing, and in worst case, bursting and fire, etc. The actual Product Profile is available at www.epcos.com/publications.