News
...
Split Meters (DRDHC) 1/3 Phase

Single Phase Pole-Mounted Meter

Description

AKU S10 - Split-meter of electric energy single-phase static bidirectional direct switching. It is designed to measure electrical energy (active and reactive, forward and reverse), evaluate instantaneous active, reactive, apparent power and a number of other parameters in single-phase AC networks with a voltage of 230 V. Allows centralized data collection over 0.4 kV lines or 868 MHz radio channel. The meter is equipped with a power The AKU S10 meter is mounted directly on a power pole using a specially designed bracket or suspended from an insulated wire. The CIU8 user display is used to display information about the measured parameters.

Charateristics

Specifications :
Accuracy class:- Active (reactive) energy 1 (2)
Number of Accounting Directions Export, import
Constant Counter:- Active Energy- Reactive Energy 1000 cps/(kWh)1000 cps/(kvar∙h)
Sensitivity:- Active (reactive) energy 0.02 (0.025) A
Self-propelled:- no more than one pulse per time, for active (reactive) energy 33 (26) min
Minimum Current:- Active (reactive) energy 0.25 (0.25) A
Base (Maximum) Current 5 (80) A
Nominal Voltage and Operating Range 230 V ± 20 %
Rated Frequency 50 Hz
Power consumed by each:- parallel circuit, not more than - series circuit, not more than 1.6 W (10 V∙A) 0.1 V∙A
Self-consumption current by phases, not more than 0.045 A
Communication Interfaces PLC LV (0.4 kV power line) for communication with RTR;- 868 MHz radio modem for communication with RTR (alternative to PLC LV channel), as well as for communication with CIU8. B-2-1;- optical port for local parameterization
Sensors Neutral current sensor for DIFF detection. current:- Magnetic field sensor (Hall sensor)
Load Control Relay, Main:- Current Rating of Contact Group - Switching Wear Resistance 80 A10∙103
Number of tariffs in the schedule / Number of switches per day, no more than 6 / 24
Hours per day at + 25 °C, no worse ± 0.5 s/day
The accuracy of the watch ranges from -40 °C to + 70 °C, no worse ± 5.0 s/day
Interval between verifications 16 years
Degree of sheath protection IP 65
Connection type Direct Activation
Service life of the metering device:- battery life, not less than - average service life, not less than - average time between failures of the meter, not less than 16 years 30 years 230,000 h
Dimensions (134×132×75) mm
Weight, no more:- Meter kit without CIU8 display. B-2-1 - Meter kit with CIU8 display. B-2-1 0.9 kg1.0 kg